Item | Specification and Technical Data | |
Main powerconnection | Input voltage U1 | 220V/380V/500/690V±15%;signal/three-phase power |
Input frequency f1 | 50...60Hz ±5Hz | |
Output voltage U2 | 0...U1 (V)(The maximum output voltage equals the input power voltage.) | |
Output frequency f2 | 0-1000Hz | |
Carrier frequency | 2-8 KHz (The device can intelligently and automatically make optimal adjustment according to load characteristics and drive temperature.) | |
Input voltage unbalance degree | Maximum: ±3% of rated inter-phase input voltage | |
Efficiency | ≈ 98% (when operating at rated power) | |
Basic functions | Speed range | 0-1000Hz ( 0~30000 rpm,60000rpm is optional ) |
Resolution of given speed | Digital setting:1RPM Analog setting:0.025%of maximum RPM | |
Control mode | SVC control / FVC vector control | |
Starting speed | 200% @ 0.25Hz@ SVC control200% @0Hz@ FVC contro | |
Speed ratio | 1 :200 @SVC control 1 :3000 @FVC control | |
Steady-speed precision | ±0.5% @ SVC control ±0.01% @ FVC control | |
Overload capacity | Heavy load application:60s at 150% rated current @40°C.The time depends on the drive temperature under other conditions. General application:60s at 120% rated current @40°C.The time depends on the drivetemperature under other conditions. | |
Torque boost | Automatic torque boost. Manual torque boost 0.1%-30% | |
Acceleration and deceleration curves | straight-line or S-curve acceleration and deceleration mode Two acceleration time values.The acceleration and deceleration time range :0.0s-650.00s | |
Simple PLCfunction | Achieve operationof up-to-16-stages speed(via built-in PLC or control terminals) | |
Built-in PID | Conveniently achieve the process control close-loop control system | |
Automatic voltageregulation (AVR) | When the grid voltage changes,the device automatically maintainsconstant output voltage. | |
Overvoltage and overcurrent stall control | The current and voltage are automatically limited during running to avoid jump faults due to frequent overcurrent and overvoltage | |
Enhancements | Torque limiting and contro | The torque is automatically limited operating (to avoid frequent overcurrent jumping fault due to too large torque). |
Protection function | Output shortcircuit protection,input &output phase loss protection,overcurrent protection,overvoltage protection,undervoltage protection,overheat protection,overload protection,brake chopper overload protection,brake chopper shortcircuit protection,brake resistor overload protection | |
Non-stop during transient interruption | Keep the frequency converteroperating in a short time (by reducing feedback energy compensation voltageat the moment of power outage).The duration depends on the mechanical inertia of the load at that time. | |
Speed tracking restart | Asynchronous motor speed tracking start can be realized ( standard ) and synchronous motor speed tracking start (optional) | |
Timing control | Timing control function.The time range and precision is 0.0-6500.0(min). | |
Switching multiple motors | Support switching among four groups of motor parameters. | |
Bus communication | The standard configuration uses the built-in Modbus/communication,which can be extended to Profibus-DP,CANopen bus communication. Etc. | |
Intelligent temperature control | Full cover system temperature testing,intelligent real-time IGBT chip temperature monitoring,and intelligent and optimized adjustment of the carrier and current based on drive temperature changes | |
Type of encoders supported | Support differential encoders,collector open encoders,rotary transformer encoders ,and Sin-Cos Encoders | |
Communication linkage synchronization | Easily realize multi-motor synchronous transmission,and can freely choose to realize the linkage balance of multi-motor by current,torque or power. | |
Debug window | Visual parameter debugging,fault display and waveform monitoring can be easily realized through the PC terminal etc. | |
Item | Specification and Technical Data | |
Input Output Interface | Command input mode | Coswintrotchelkdeym otuaardllyinput,control terminal input,bus communication input,which can be switched mutually. |
Speed reference mode | Digital giving,analog voltage (current)giving,pulse giving,bus communication giving and PID giving,which are mutually switched. | |
Input terminal (input) | The followings are included in standard configuration : 6 (F0) / 7 (F1 and above) digital input terminals,where, DI6 (F0) Dl7 (F1 and above)supports the maximum of 50 kHz high-speed pulse input. 2 (F0) /3 (F1 and above) analog input terminals (where, at least 2 supports 0-10V voltage input or 0-20 mA or 4-20mA voltage input) The followings are extended as cards : 5 digital input terminals 2 analog input terminals,supporting input of -10V to+10V voltage (Optional) | |
Output terminal (output) | The followings are included in standard configuration: 1 high-speed pulse output terminal (supporting 0-50 kHZ square signal output) 1 (F0) /2 (F1 and above) digital output terminals 1 (F0) /2 (F1 and above) relay output terminals 1 (F0) /2 (F1 and above) analog output terminals (supporting0-10V voltage output or 0-20mA or 4-20 mA voltage output) | |
Display and control | Man-machine interface | F0 built in fixed LED keypad,and LCD keypad is optional. F1 and above is built in standard smart LCD keyboard,LED keypad is optional |
Parameters duplicating | Rapidly duplicating parameters via the LCD control keyboard | |
Application environment | Application site | Indoor,free of direct sunshine,dusts,corrosive gases,flammable gases,oil mist,water vapor,drip or salts |
Altitude | At 0-1000m ; When the altitude is 1000-4000m, the capacity is reduced by 1% as the altitude rises by 100m. (consult professionals for more accurate values) | |
Operation ambient temperature | -10℃to+40℃ (when the ambient temperature is 40℃-55℃,the drive is automatically derated to achieve self-protection) | |
Relative humidity | Less than 95%RH. No droplets condensed (condensation) | |
Sinusoidal vibration | (IEC 60068- 2/ - 6.TestFc) Max.0.1mm (5 to 13.2Hz); max.7m/S 2 (13 .2 to 100 Hz) sinusoidal vibration (F0-F7) Max.0.1mm (10 to 57Hz); max.l0m/S 2 (57 to 150 Hz) sinusoidal vibration (F8-F9) | |
Impact | Not and allowed (during operation); maximum 100m/S2, 11ms (during storage transportation with packing) | |
Free fall (Max.) | Not allowed (during operation); with packing : 100cm @F0-F2A, 76cm @F3-F4,46cm @F5-F7, 15cm @F8-F9 | |
Storage &transportation temperature | -40℃to+70℃(-40 to+158°F) | |
Protection grade | IP20 (UL-open type), (the medium cavity with air vents on two sides for some F0**models) Electrical cavity full closed design for small-and medium-power models, Top/Left and right sides can reach IP40 | |
Cooling mode | Forced air cooling of the interior fan.The air flows from bottom to top.Air-cooled radiator. | |
Application standard | IEC 61800-3 , IEC 61800-5-1 ; GB12668 (see the nameplate for details). | |